NP800系列
NP800系列產品為CEE繼電器全新升級產品,NP800繼電器為人、網絡和電氣裝置提供保護,并允許與SCADA系統(tǒng)通信。多功能NP800繼電器除了提供以前系列的常規(guī)保護功能外,還提供網絡電量的監(jiān)視、測量和記錄。
產品簡介
我們在靜電繼電器和數字繼電器的電網保護領域的技術訣竅使新一代產品的開發(fā)符合最苛刻的質量標準和最新的技術概念。這項專長的結果之一是數值NP800繼電器范圍。
NP800繼電器為人、網絡和電氣裝置提供保護,并允許與SCADA系統(tǒng)通信。多功能NP800繼電器除了提供以前系列的常規(guī)保護功能外,還提供網絡電量的監(jiān)視、測量和記錄。
NP800系列的共同特征:
輔助電源范圍:19V至70V或85V至255V(交流或直流)
2個設置表
自診斷:RAM、ROM、EEPROM、輸出繼電器、A/D轉換器、輔助電源、軟件執(zhí)行時間監(jiān)控
可選I/O擴展板(當存在定向功能時包括)
設置、讀取、測量和記錄均在本地或遠程可用。
符合IEC 60255-4標準。
斷路器故障監(jiān)測
事件記錄:250個事件,10毫秒分辨率
4通信貿易格式的干擾記錄
Our know-how in the domain of electrical network protection by static and numerical relays has led to the development of new generations of products that comply with the most demanding quality standards and the most recent technological concepts. One of the results of this expertise is the numerical NP800 relay range.
The NP800 relays provide the protection of people, networks and electric installations and they allow communication with SCADA systems. As well as the usual protection functions of former ranges, the multifunctional NP800 relays provide monitoring, measurement and recording of the network electrical quantities.
Common characteristics for the NP800 range:
Auxiliary supply ranges: 19V to 70V or 85V to 255V (AC or DC)
2 setting tables
Self-diagnosis: RAM, ROM, EEPROM, output relays, A/D converters, auxiliary supply, monitoring of software execution time
Optional I/O extension board (included when directional function is present)
Setting, reading, measuring and recording are all available locally or remotely
Complies with IEC 60255-4 standard.
Monitoring of circuit breaker failure
Event recording: 250 events, 10ms resolution
4 disturbance recordings in COMTRADE format
Dispositivo | ANSI | Descrizione | |
---|---|---|---|
NPG800 | 21, 24, 27, 32, 37, 40, 46, 49, 50, 51, 50V, 51V, 59, 59N, 64, 81, 50BF, 74TC, 86 | Multi function generator protection | |
NPI800 | 46, 46BC, 49, 50, 50N, 50BF, 51, 51N, 86, 74TC | Phase and Earth Overcurrent Protection | |
NPID800 | 46, 46BC, 49, 50, 50N, 50BF, 51, 51N, 67, 67N, 86, 74TC | Phase and Earth Overcurrent Protection with directional criteria | |
NPIH800 | 50N, 50NBF, 51N, 86, 74TC | Earth Overcurrent Relay | |
NPIHD800 | 50N, 50NBF, 51N, 67N, 86, 74TC | Earth Overcurrent Relay with directional criteria | |
NPU800 | 27, 27P, 47, 59, 59N, 74TC, 81, 86 | Voltage and Frequency Relay | |
NPUH800 | 59N, 86, 74TC | Residual Overvoltage Relay (Neutral Displacement Relay) | |
NPM800 | 37I, 46, 48, 49, 5/49, 50, 50BF, 51LR, 51N, 66, 86, 74TC | Multi function motor protection | |
NPRG810-1G NPRG810-4G | 25, step up transformer adaptation | Generator Synchro-check relay | |
NPRG860 NPRG870 | 25, 90, step up transformer adaptation | Automatic synchronizer device for up to 4 generators | |
NPSC800-1 NPSC800-2 | 25 25 + network managment | Network Check Synchronizing Relay | |
NPW800 | 32, 37, 27, 59, 59N, 55, 81, 86, 74TC, BF |